MC Cable


Type and designation

Type

designation

MC

Lightweight Aluminum Interlocked Armored Cable

Deion of the pure
MC Cable is suitable for use as follows:
? Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
? Power, lighting, cool, and signal circuits.
? Fished or embedded in plaster.
? Concealed or exed installations.
? Environmental air-handling spaces per NEC 300.22 (C).
? Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
? As aerial cable on a messenger.
? Installation in cable tray and approved raceways.
? Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D) (2).
? Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.

Standard
UL 83, UL 1063, UL 1569

Features
1, Reduces installation costs up to 50% over pipe and wire.
2, Lightweight aluminum armor--as much as 45% lighter than steel MC Cable.
3,UL Classified 1, 2, and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113, W-L-3117,W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173, C-AJ-3202, C-AJ-4065,C-AJ-4066, F-C-3038.
4, Cable reverse wound on reel for ease of pulling and installation. When pulling from coils, pull from inside to ensure ease of installation.

Specification and Construction 

MC Cable is constructed with soft-drawn copper, Type THHN/THWN conductors rated90°Cdry/75°Cwet, ailable in sizes 14 AWG through 750 kcmil, and a green insulated grounding conductor (sizes 1/0 AWG and larger furnished with bare grounding conductor). The conductors are cabled together and a binder tape bearing the print legend is wrapped around the assembly. Aluminum interlocking armor is applied over the assembly. Refer to color chart for conductor color sequence.




Conductor Size (AWG)

Solid or Stranded

Grounding Conductor Size (AWG) and Stranding

Overall Diameter (inches)

Approximate Weight

Ampacity

Standard Package

lbs./1000'

kg./km.

75°C

90°C

Coil (feet)

Reel (feet)

14/4

Solid

14 sol

0.496

135

201

15

15

250

1000

12/2

19

12-19

0.508

119

178

20

20

250

1000

12/2

Solid

12 sol

0.480

115

171

20

20

250

1000

12/3

19

12-19

0.543

147

220

20

20

250

1000

12/3

Solid

12 sol

0.512

141

211

20

20

250

1000

12/4

19

12-19

0.579

176

262

20

20

250

750

12/4

Solid

12 sol

0.547

169

252

20

20

250

750

10/2

19

10-19

0.579

170

254

30

30

250

750

10/2

Solid

10 sol

0.550

165

246

30

30

250

750

10/3

19

10-19

0.622

213

318

30

30

250

500

10/3

Solid

10 sol

0.590

207

309

30

30

250

500

10/4

19

10-19

0.669

257

383

30

30

250

500

10/4

Solid

10 sol

0.634

250

373

30

30

250

500

8/2

19

10-19

0.660

230

343

50

55

200

500

8/3

19

10-19

0.724

301

449

50

55

200

500

8/4

19

10-19

0.790

372

555

50

55

125

500

6/2

19

8-19

0.753

329

491

65

75

125

500

6/3

19

8-19

0.825

433

646

65

75

125

500

6/4

19

8-19

0.900

537

801

65

75

100

500

4/3

19

8-19

0.956

624

931

85

95

100

500

4/4

19

8-19

1.056

789

1178

85

95

100

500

3/3

19

6-19

1.032

776

1158

100

110

100

500

3/4

19

6-19

1.139

980

1462

100

110

100

500

2/3

19

6-19

1.089

915

1365

115

130

100

500

2/4

19

6-19

1.207

1164

1737

115

130

100

500

Note: Ampacities are based on Table 310.16 of the NEC, 2005 Edition.
Allowable ampacities shown are for general use as specified by the National Electrical Code, 2005 Edition, Section 310.15.If the equipment is marked for use at higher temperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C).75°C- When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90°C- For ampacity derating pures.
Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of 0.80 when the neutral is considered a current-carrying conductor.
A vailable in sizes up to 750 kcmil.

COLOR CODING Standard Products

No. of Conductors

Color Sequence 

2

Black, White

3

Black, White, Red

4

Black, White, Red, Blue

Grounding Conductor

Green or bare

Other special colors are ailable subject to economic order quantity.